| Availability: | |
|---|---|
| Quantity: | |
FBR12-100
FOBERRIA
85072000
The FOBERRIA FBR12-100 is a 12V sealed lead acid AGM battery for UPS backup power. Its 100Ah rating is measured at the 20-hour rate. Defined charging limits, F14 terminals and a compact case support detailed battery replacement assessment.
A capacity label alone does not establish UPS autonomy. FBR12-100 provides separate ratings for 20-hour, 10-hour and one-hour discharge. Buyers should compare the required load duration with the matching rating before choosing a battery quantity.
FBR12-100 specification
Parameter | Condition / detail | Value |
|---|---|---|
Battery Model No. | — | FBR12-100 |
Nominal Voltage | — | 12V |
Capacity(25ºC) | 20HR(10.5V) | 100Ah |
Capacity(25ºC) | 10HR(10.5V) | 85Ah |
Capacity(25ºC) | 1HR(9.6V) | 60Ah |
Dimension | Length | 330±1mm |
Dimension | Width | 171±1mm |
Dimension | Height | 214±1mm |
Dimension | Total height | 220±1mm |
Approx. Weight | — | 29.5kg ±5% |
Terminal type | — | F14 |
Internal resistance(Fully charged,25ºC) | — | Approx. 4.5mΩ |
Capacity affected by temperature(20HR) | 40ºC | 102% |
Capacity affected by temperature(20HR) | 25ºC | 100% |
Capacity affected by temperature(20HR) | 0ºC | 85% |
Capacity affected by temperature(20HR) | -15ºC | 65% |
Self-discharge(25ºC) | 3month | Remaining Capacity:91% |
Self-discharge(25ºC) | 6month | Remaining Capacity:82% |
Self-discharge(25ºC) | 12month | Remaining Capacity:65% |
Nominal operating temperature | — | 25ºC±3ºC(77ºF±5ºF) |
Operating temperature range | Discharge | -15ºC-50ºC(5ºF-122ºF) |
Operating temperature range | Charge | -10ºC-50ºC(14ºF-122ºF) |
Operating temperature range | Storage | -20ºC-50ºC(-4ºF-122ºF) |
Float charging voltage(25ºC) | — | 13.6 to 13.8V(Temperature compensation:-18mV/ºC) |
Cyclic charging voltage(25ºC) | — | 14.5 to 15V(Temperature compensation:-30mV/ºC) |
Max charging current | — | 30A |
Max discharging current | — | 800A(5sec.) |
Designed floating life(20ºC) | — | 12years |
At 25°C, the battery delivers 100Ah over 20 hours to 10.5V, or 85Ah over 10 hours to 10.5V. The one-hour entry is 60Ah to 9.6V. These different test conditions should remain attached to the capacity figures during comparison.
The case measures 330 ±1mm long, 171 ±1mm wide and 214 ±1mm high. Total height reaches 220 ±1mm. Allow space for the installed connections as well as the case. Approximate mass is 29.5kg ±5%; the terminal designation is F14.
At 25°C, the specified float range is 13.6–13.8V, with temperature compensation of −18mV/°C. This is the relevant charging entry for standby assessment. Charger settings should be checked against the complete battery arrangement and its operating temperature.
The cyclic charge specification is 14.5–15V at 25°C, with −30mV/°C compensation. Maximum charging current is 30A. The separate 800A discharge figure applies for five seconds; it does not describe sustained backup output.
The 20-hour capacity reference falls to 85% at 0°C and 65% at −15°C. It is 100% at 25°C and 102% at 40°C. Backup sizing should therefore include the battery-room temperature, rather than applying the room-temperature rating everywhere.
Remaining capacity at 25°C is listed as 91% after three months, 82% after six months and 65% after twelve months. Designed floating life is 12 years at 20°C. This design reference is separate from a warranty or a promised replacement interval.
This model belongs to the FOBERRIA VRLA UPS battery range. For an existing UPS, record the DC bus voltage, installed battery count and required backup duration. A matching nominal voltage alone is insufficient to establish a replacement configuration.
FBR12-100 is rated 100Ah at 25°C over 20 hours to 10.5V. It is not a guarantee of 100Ah at every discharge speed; its one-hour rating is 60Ah to 9.6V.
The FBR12-100 float specification is 13.6–13.8V at 25°C. The stated temperature compensation is −18mV/°C, so charger review must include battery temperature.
No. The FBR12-100 table gives 800A for five seconds only. Sustained UPS sizing requires load and discharge information beyond this short-duration limit.
The case height is 214 ±1mm, but overall height is 220 ±1mm. Check the compartment against total height and the installed F14 connection arrangement.
At the 20-hour rate, capacity is listed as 85% at 0°C and 65% at −15°C. Use the expected battery temperature when assessing the backup requirement.
The table specifies a 12-year designed floating life at 20°C for FBR12-100. It does not define a 12-year warranty; commercial warranty terms require separate confirmation.